- What does a silica gel breather do on a transformer?
The silica gel breather dries the air that enters the transformer when the oil contracts on cooling, so that atmospheric moisture does not reach the oil or the insulating paper.
- What does a winding temperature indicator show?
A winding temperature indicator estimates the temperature of the hottest spot in the winding by adding to the oil temperature an increment proportional to the load current; it does not measure the winding directly.
- What does the IEC 60076 series cover?
IEC 60076 is a series of international standards on power transformers, organized in parts covering general requirements, temperature rise, insulation, loading capability, short circuit, noise and other aspects.
- What does the IEEE C57.12.90 test code describe?
IEEE C57.12.90 is a test code for liquid-immersed distribution and power transformers and regulators: it defines how routine and design tests are performed and calculated.
- What does the IEEE C57.152 field testing guide set out?
IEEE C57.152 is a guide to diagnostic field testing of fluid-filled transformers, regulators and reactors: it describes which tests to apply and how to perform and interpret them.
- What guidance does the IEEE C57.91 loading guide give?
IEEE C57.91 is a guide on how to estimate temperatures, insulation aging and loading capability of mineral-oil-immersed transformers under different load cycles and ambient conditions.
- What is a Buchholz relay for?
The Buchholz relay detects accumulated gas or a sudden surge of oil in the pipe between the tank and the conservator, and gives an alarm or trips on internal faults.
- What is a transformer tap selector with transition resistors?
It is the on-load tap changer system in which a selector chooses the tap with no current flowing and a diverter switch with transition resistors makes the change without interrupting the load or short-circuiting turns.
- What Is Core Saturation?
Core saturation occurs when the flux exceeds the limit the steel can carry in proportion to the current: permeability then falls, the magnetizing current spikes and the waveform becomes distorted.
- What Is Evaluated in a Site Acceptance Test?
A site acceptance test verifies that the transformer arrived undamaged, was installed correctly and works as specified: inspection, electrical tests, oil tests and verification of protections and accessories.
- What Is Leakage Flux?
Leakage flux is the part of the magnetic flux that does not link both windings; it determines the leakage reactance, limits the short-circuit current and produces additional forces and losses.
- What Is the Angular Displacement Between Primary and Secondary?
Angular displacement is the phase angle between the high-side and low-side voltages; it arises because delta and wye connections relate line voltages and winding voltages differently.
- What is the conservator tank for?
The conservator tank absorbs the expansion and contraction of the oil, keeps the main tank full and limits the oil surface exposed to air.
- What Is the Cooling Class of a Transformer?
The cooling class is a letter code that describes which fluid cools the transformer and how it circulates, for example oil in natural circulation with natural or forced air; it defines the capacity at each cooling stage.
- What Is the Excitation Current of a Transformer?
Excitation current is the current a transformer draws from its source with the secondary open and at rated voltage; it creates the core flux and covers the core losses, and its waveform is not sinusoidal because the magnetic material is not linear.
- What Is the Hot Spot in a Winding?
The hot spot is the hottest zone of the winding, normally in the upper part of the conductors; it sets the aging rate of the insulation and, therefore, the loading capability of the transformer.
- What Is the K-Factor of a Transformer?
The K-factor quantifies how much additional heating a load with harmonics produces in a transformer; a K-rated transformer is designed to withstand nonlinear loads with reduced eddy-current losses.
- What Is the Percent Impedance of a Transformer?
Percent impedance is the voltage that must be applied to the primary, with the secondary short-circuited, for rated current to flow, expressed as a percentage of rated voltage; it sums up the internal voltage drop and limits fault current.
- What Is the Permissible Temperature Rise in a Transformer?
Permissible temperature rise is the increase in winding and oil temperature above ambient that the design allows at rated load, and it is set so that the cellulose insulation achieves its intended thermal life.
- What Is the Vector Group of a Three-Phase Transformer?
The vector group of a three-phase transformer indicates how its windings are connected, in delta, wye or zigzag, and what phase shift results between the high-side and low-side voltages, using a code of letters and a number.
- What is transformer inrush current and what effects does it have?
Energizing current, or inrush, is a transient magnetizing current far above rated current that appears when a transformer is connected and its core saturates, and it can cause protection trips, voltage sags and mechanical stresses.
- Why do oil leaks occur in a transformer?
Oil leaks originate mainly at aged gaskets, welds or flanges that have lost their tightness, because of thermal cycling, vibration and corrosion; they indicate a loss of tightness and can let moisture in.
- Why does a bushing fail?
Bushings fail mainly because of moisture penetrating the insulation, partial discharges that erode it, overheated connections and external contamination, and the failure can be violent.
- Why does a transformer hum louder than normal?
Normal hum comes from magnetostriction in the core; if it increases or changes tone, it points to overexcitation, harmonics, loose components or resonances, and must be investigated.
- Why Does Winding Insulation Paper Deteriorate?
Insulation paper deteriorates mainly because of temperature, moisture and oxygen: the cellulose chains break, the paper loses mechanical strength and releases water, acids and gases, and the damage is irreversible.