What does the IEEE C57.12.90 test code describe?

IEEE C57.12.90 is a test code for liquid-immersed distribution and power transformers and regulators: it defines how routine and design tests are performed and calculated.

What it is about

The document is a test code. It does not set the values a transformer must meet; other standards in the IEEE C57 series, such as those on general requirements, do that. What the code does is describe how tests are performed, what conditions apply, how readings are corrected and how results are calculated, so that two laboratories obtain comparable results.

Which tests it covers in general terms

  • Winding resistance and its temperature correction.
  • Transformation ratio, polarity and phase relation.
  • No-load losses and excitation current.
  • Load losses and impedance.
  • Dielectric tests: applied voltage, induced voltage, impulse and partial discharge measurement.
  • Temperature rise.
  • Noise level, short circuit and other special tests.

How it relates to the engineer’s work

When a specification calls for a test “in accordance with the code”, the measurement procedure, connections, permissible instruments and data treatment come from this document. This is useful when comparing a factory report with a field test: if the method differs, the figures may not be comparable.

An example of use

When load losses are measured, the result depends on the winding temperature. The code indicates how to refer that measurement to a reference temperature. If a report does not state the reference temperature or the correction method, comparing it with another report becomes meaningless.

When it does not apply

  • To dry-type transformers, which have their own test code.
  • To instrument transformers, reactors and other equipment with their own documents.
  • As a substitute for field diagnostic guides, which have a different purpose.

The code is revised periodically, and its methods and structure change. The current edition, or the one cited in the contract, must be consulted. This guide describes only the general scope.

Warning: high-voltage and short-circuit tests must be performed by qualified personnel, in suitable facilities and in accordance with the applicable safety regulations.