How it is defined
If the secondary of a transformer is short-circuited and a reduced voltage is applied to the primary, that voltage is adjusted until rated current flows. The ratio of the applied voltage to rated voltage, as a percentage, is the percent impedance, also called short-circuit voltage. It is referred to the transformer’s own rated power and voltage.
Where it comes from
It is the sum of two effects: leakage reactance, due to the flux that does not link both windings, and the resistance of the conductors. In power transformers reactance dominates, determined by the geometry of the windings and the distances between them.
What consequences it has
- Short-circuit current: with a very strong source, the secondary fault current is approximately the rated current divided by the per-unit impedance. A lower impedance gives more fault current.
- Voltage regulation: the voltage drop under load grows with impedance and depends on the power factor of the load.
- Parallel operation: transformers in parallel share the load in inverse proportion to their impedances. Very different values cause one to overload before the other.
- Selection of protective devices: breaker interrupting capacity and relay settings depend on the available fault current.
- Stability and mechanics: the windings withstand mechanical stresses during faults, and these grow with the current.
How it is determined
Impedance is measured in the short-circuit test, also called the impedance test, with a low voltage and a current close to rated. The nameplate value corresponds to a reference temperature. When there is a tap changer, the impedance varies with its position.
How to interpret the result
The field measurement is compared with the nameplate and factory values, and also between phases. A noticeable deviation from the reference, or a difference between phases, can indicate displacement or deformation of the windings after a through-fault or transport. It is complemented by other tests, such as frequency response.
A high impedance is neither better nor worse: it is a compromise between limiting the fault and keeping the voltage stable under load.