Power quality and Grid Code

Clear explanations of concepts, methods, standards and measurements for engineers and technicians.

  • Direct measurement or instrument transformers in power quality

    Direct measurement is limited to voltages and currents within the analyzer's range and measurement category; at higher levels, potential and current transformers are used, which reduce the signals but add ratio error, phase error and frequency response limits.

  • Electronic regulator or constant-voltage transformer?

    An electronic regulator corrects slow voltage variations using switched taps or a servo element, with an output that keeps the input waveform; a constant-voltage (ferroresonant) transformer regulates through core saturation, isolates and tolerates brief sags, but delivers a more distorted waveform and depends on the load.

  • Fixed or automatic power factor correction?

    Fixed correction always delivers the same kvar and works when reactive demand is stable; automatic correction switches steps in and out under a controller and works when reactive demand varies during the day.

  • How are maximum demand and load factor measured?

    Maximum demand is the highest average power calculated over successive demand intervals, and load factor is the ratio of average demand to maximum demand for the period.

  • How do you determine whether harmonic distortion comes from the load or the network?

    To find out whether harmonic distortion comes from the load or the network, compare how harmonic voltage and current vary as the load changes, the direction of harmonic power flow and the background distortion present with the load disconnected.

  • How Do You Plan a Power Quality Monitoring Campaign?

    A power quality monitoring campaign is planned starting from the question it must answer: define the objective, measurement point, parameters, evaluation criterion and a duration that covers all representative operating modes.

  • How Do You Select the Connection Point for a Power Analyzer?

    The connection point of an analyzer is chosen according to the question to be answered: at the service entrance to evaluate compliance, at the sensitive load to see its effects, and at the suspect load to isolate its contribution.

  • How do you set an analyzer’s thresholds to capture voltage events?

    An analyzer's thresholds for capturing voltage events are set relative to the declared nominal voltage, with values for sags, overvoltages and interruptions, hysteresis to prevent repeated triggering, and a recording time before and after the event.

  • How Do You Size a Capacitor Bank Without Amplifying Harmonics?

    A capacitor bank is sized by calculating the kvar needed to bring the power factor to the target value and checking that its resonant frequency with the network stays well away from the harmonics present; if it does not, detuning reactors are used.

  • How do you trace the origin of a voltage sag: upstream or downstream?

    Whether a voltage sag originates upstream or downstream of the measurement point is inferred by comparing the sag with the behavior of the current: if more current flows toward the load during the event, the fault is downstream; if the current drops or does not rise, it is upstream.

  • How does a Rogowski coil work?

    A Rogowski coil is a winding with no magnetic core placed around the conductor. By Faraday's law, its output voltage is proportional to the derivative of the current, and an integrator converts it into a signal proportional to the current.

  • How does a voltage event recorder work?

    A voltage event recorder continuously calculates the RMS value per half cycle and, when it crosses a configured threshold, stores the event with its start, its duration and its residual or maximum voltage, sometimes with the waveform.

  • How does power quality analysis help reduce Joule losses?

    Power quality analysis reduces Joule losses by revealing the currents that do no useful work, such as harmonics, reactive current, and unbalance, which raise the RMS value of the current and with it the heating.

  • How does power quality monitoring justify an investment?

    Power quality monitoring is justified when its cost can be compared with what the downtime, damage, and losses it reveals are costing, and when it turns suspicions into data that support a decision.

  • How is a passive harmonic filter designed in general terms?

    A passive harmonic filter is a series LC circuit tuned close to the frequency to be removed. It offers that harmonic current a low-impedance path and keeps it from flowing into the grid.

  • How is current measured on busbars with flexible coils?

    To measure current on busbars with flexible coils, the Rogowski coil is wrapped around the busbar, the coupling is closed and the coil is connected to an integrator that converts the signal proportional to di/dt into a signal proportional to the current.

  • How is current unbalance measured in a three-phase feeder?

    Current unbalance in a three-phase feeder is measured by recording the three phase currents simultaneously, and it is expressed as the deviation from the average or, more rigorously, as the ratio between the negative-sequence and positive-sequence components.

  • How is grid frequency variation measured?

    Grid frequency variation is measured by counting the cycles of the fundamental voltage over a defined time window and comparing the result with the nominal value. Frequency reflects the balance between generation and load in the system.

  • How is neutral-to-ground voltage recorded?

    Neutral-to-ground voltage is recorded by connecting one of the analyzer's voltage channels between the two points and logging its RMS value and waveform over a representative period, always together with the neutral current.

  • How Is Power Quality Compliance Verified at the Point of Interconnection?

    To verify power quality at the point of interconnection, measure there with a standardized method over a representative period and compare the statistical results with the criteria that apply under the contract, the regulation or the chosen standard.

  • How Is Power Quality Data Aggregated into Averaging Intervals?

    Power quality data is aggregated by calculating a base quantity over short windows and combining those values, usually by root mean square, into longer intervals; minimums, maximums and events are recorded separately so that the average does not hide them.

  • How is power quality validated after installing a variable speed drive?

    Power quality is validated by comparing measurements taken before and after installing the drive, at the point of coupling and at different load levels, against the applicable criteria.

  • How is reactive power measured in unbalanced loads?

    Reactive power in unbalanced loads is measured per phase, using the voltage and current of each phase, and then summed. The delicate part is that under unbalance, total apparent power and total power factor have several definitions that are not equivalent.

  • How is the crest factor of a current measured?

    The crest factor of a current is measured as the ratio of its peak value to its true RMS value in the same window. A pure sine wave gives the square root of two, and higher values indicate the narrow peaks typical of nonlinear loads.

  • How is the effect of a distributed generation plant on the local grid assessed?

    It is assessed by comparing the state of the local grid with and without the plant, at the connection point, reviewing voltage level, power flows, protections, waveform quality, and behavior during faults.

  • Online or line-interactive UPS against grid variations?

    An online UPS always feeds the load from the inverter and isolates it from the grid, with no transfer time; a line-interactive UPS passes regulated grid voltage and switches to battery only on a failure, with a brief transfer time.

  • Passive or active harmonic filter?

    A passive filter is a tuned LC circuit, simple and economical, that traps specific harmonics; an active filter measures the load current, injects the opposite current using power electronics and covers a wide spectrum adaptively.

  • Portable analyzer or fixed meter: when is each one the right choice?

    A portable analyzer is the right choice for investigating a problem, measuring at several points for limited periods or supporting a diagnosis; a fixed meter is the right choice when continuous monitoring, history and ongoing compliance are needed at a defined point.

  • What Are Displacement Power Factor and True Power Factor?

    Displacement power factor is the cosine of the angle between the fundamental voltage and current; true power factor is the ratio of active power to total apparent power, and it includes the effect of harmonics.

  • What are interharmonics and where do they come from?

    Interharmonics are voltage or current components whose frequency is not an integer multiple of the fundamental frequency; they come from loads whose current varies out of synchronism with the network, such as frequency converters, arc furnaces and modulated drives.