What does a silica gel breather do on a transformer?

The silica gel breather dries the air that enters the transformer when the oil contracts on cooling, so that atmospheric moisture does not reach the oil or the insulating paper.

Why a transformer breathes

Oil expands when the transformer heats up and contracts when it cools. In units with a conservator tank, this change in volume is compensated by air leaving or entering through the top of the conservator. If that air entered untreated, it would carry water vapor with it, and moisture degrades both the oil and the winding paper.

How it does its job

The incoming air first passes through a chamber containing silica gel, a desiccant that retains water vapor on its surface. At the bottom, many breathers include an oil seal: a small cup that forces the air to pass through oil and prevents air from continually entering by diffusion when there is no change in volume.

The color indicator

Part of the silica gel contains an indicator that changes color as it absorbs moisture. The color scheme depends on the type of gel and the manufacturer: some gels go from blue to pink and others from orange to colorless. The important thing is to know the scheme of the installed gel and to replace or regenerate it when most of it has changed color, following the manufacturer’s instructions.

What the engineer sees in the field

  • Gel that saturates quickly usually indicates a lot of air exchange: wide load cycles, or a leak that lets air in without passing through the breather.
  • Gel that never changes may mean that air is not circulating through it: a blocked seal or an obstructed connection.
  • Seal oil below the marked level, or contaminated, reduces its effect.

When it does not apply

Hermetically sealed transformers, or those with a diaphragm or bladder in the conservator, limit or prevent contact between oil and air. In these cases the breather, if there is one, protects the air chamber above the membrane. Dry-type transformers do not use this device.

What to check first

  1. Gel color and seal oil level.
  2. Tightness of the joint between the breather and the conservator.
  3. Oil moisture measured in the laboratory, which reveals whether the system is working.

It is an inexpensive component, but neglecting it allows the insulation to take on moisture, and that moisture is difficult to remove afterward.