What is the conservator tank for?

The conservator tank absorbs the expansion and contraction of the oil, keeps the main tank full and limits the oil surface exposed to air.

The basic function

Oil volume changes with temperature. A transformer goes from cold to hot, and the oil needs room to expand without pressurizing the tank or spilling. The conservator is a vessel placed above the main tank, connected by piping, that provides this expansion volume. As it cools, the oil returns to the main tank, which stays full.

What a conservator gives us

  • The main tank and the windings always remain covered with oil.
  • The oil surface in contact with air is reduced to that of the conservator, much smaller than if the tank had an air cushion.
  • Gases generated in a fault rise through the pipe toward the conservator and pass through the Buchholz relay, which allows them to be detected.

How it is isolated from the air

There are several solutions:

  • Open conservator with breather: air enters through a silica gel breather that dries it.
  • With bladder or diaphragm: a flexible membrane separates the oil from the air, so that the oil has no contact with the atmosphere.

Separation reduces oil oxidation and moisture absorption, and it is preferred when the aim is to extend insulation life.

Associated components

  1. Oil level indicator, with temperature-dependent marks.
  2. Buchholz relay in the connecting pipe.
  3. Silica gel breather or equivalent system.
  4. Drain and sampling valve, for removing sediment and settled water.

What is seen in the field

An oil level that does not follow temperature can mean a stuck bladder, a jammed indicator or a leak. A sustained low level points to oil loss. A very high level at low load suggests overfilling or a poorly calibrated indicator. In conservators with a bladder, a ruptured bladder lets air and moisture into the oil, and moisture analysis reveals it.

When it does not apply

Sealed transformers with a hermetic tank have no conservator: the change in volume is absorbed by the corrugated tank walls or by a gas cushion. The choice depends on the size of the equipment and the level of protection sought.