What Is the Angular Displacement Between Primary and Secondary?

Angular displacement is the phase angle between the high-side and low-side voltages; it arises because delta and wye connections relate line voltages and winding voltages differently.

Where the angle comes from

In a wye connection, the voltage between two lines is the difference of two phase voltages, so it leads one of them by thirty degrees. In a delta connection, the line voltage is simply the winding voltage. When one side is delta and the other wye, each line on one side relates to a different winding on the other, and this results in a phase shift that is a multiple of thirty degrees. With the same connections on both sides, the phase shift can be zero or one hundred eighty degrees, depending on polarity and connection order.

How it is expressed

It is indicated by the clock number of the vector group: each hour on the clock equals thirty degrees. The high-side voltage is taken as the reference, and the angle of the low-side voltage is established relative to it. The sign, lead or lag, depends on the convention used, and the one that applies must be checked in each case.

Why it matters

  • Paralleling transformers or networks: if the angles do not match, the voltage difference between the sides being joined produces an enormous circulating current, limited only by the impedances.
  • Rings and meshed networks: the phase shifts of the transformers in the loop must add up to zero.
  • Differential protection: the current on one side is phase-shifted relative to the other, so it is compensated through the connection of the current transformers or numerically in the relay. If it is not compensated, the protection sees a difference even with no fault.
  • Synchronization: when a generation source is connected, the transformer phase shift enters into the angle measurement.
  • Metering and control: devices that compare voltages on both sides need to know the angle.

What the engineer sees

The phase shift is verified during commissioning with a ratio and phase test, or it is measured with a phase instrument on both sides and compared with the nameplate. A phase shift different from the expected one or a reversed phase sequence means the connections must be reviewed before energizing.

Difference from the vector group

The vector group describes how the windings are connected and sums up the angle. Angular displacement is the consequence that is measured and taken into account in the network.