Normal hum
Every energized transformer hums. As they are magnetized, the core laminations change dimension slightly (magnetostriction), and this change occurs in each half-cycle, so the main tone is twice the grid frequency, along with its harmonics. Under load, the electromagnetic forces in the windings contribute an additional component.
What causes an increase
- High voltage or overexcitation: more flux in the core means greater magnetostrictive deformation and more noise, which grows quickly as saturation approaches.
- Harmonics and DC component: nonlinear loads, or direct currents of geomagnetic origin or from converters, distort the flux and add tones.
- Loose core or clamping: loss of tightness in bolts, beams or shims allows the laminations to vibrate.
- Loose parts: covers, shields, radiators, ducts or cabinets that vibrate sympathetically.
- Resonance: when the excitation frequency matches a natural frequency of the structure, the tank or the accessories amplify the noise.
- Support and mounting: rigid bases transmit vibration to buildings; degraded dampers let it through.
What the engineer observes
- Whether the change was gradual or sudden, and whether it coincides with a change in load, voltage or grid configuration.
- The character of the sound: continuous hum, knocking, rattling or whistling.
- The operating voltage against the rated voltage, and the harmonic content of the load.
- The frequency spectrum of the sound or vibration, which shows whether core harmonics or components of another nature predominate.
What to check first
First, the electrical conditions: voltage and harmonics. Next, the fastening of accessories and cabinets, which is the easiest thing to correct. If the noise persists with an electrical cause ruled out, the core tightness is investigated during an outage. Irregular noise or crackling, especially if it coincides with gases in the oil, may indicate internal discharges and requires immediate attention.
Warning: do not approach an energized transformer to inspect it. Internal inspection or inspection of high-voltage accessories is a matter for qualified personnel, in accordance with the applicable regulations.