The problem it solves
Changing taps with the transformer under load demands two things at once: not interrupting the load current, and not short-circuiting the turns between two adjacent taps. If one contact opened before the next one closed, the load would be cut with an arc; if both contacts were closed with nothing in between, a very high current would circulate through the bridged turns. The transition resistor limits that circulating current during the instant when both taps are connected.
How it is organized
- Selector: chooses the next tap. It operates without carrying the load current, because that branch is already free.
- Diverter switch: transfers the load from one tap to another. It is the element that actually breaks and makes current, and where the arc forms.
- Transition resistors: inserted for a very short time during the change. They are sized for brief duty, not continuous duty.
- Preselector (if present): reverses or disconnects the regulating winding to extend the range with the same taps.
Simplified sequence
- The selector prepares the adjacent tap while the load flows through the present one.
- The diverter switch connects a resistor into the path; the load is shared between both taps through resistors.
- When the movement is complete, the load remains only on the new tap and the resistors are taken out.
The entire process is driven by a stored-energy mechanism, so that once started, the change is completed even if the motor supply fails.
What is seen when it fails
- Contact wear and coking, with increased resistance in the load path.
- Transition resistors that are damaged or out of the expected value, visible in the waveform of a dynamic measurement.
- Diverter compartment oil degraded by arcing, with gases and carbon; this is monitored separately from the main tank oil.
As a mechanical component that interrupts current, it requires maintenance according to the manufacturer and the number of operations.
Warning: work on tap changers and on energized or recently de-energized transformers must be carried out by qualified personnel in accordance with the applicable regulations.