An estimate, not a direct measurement
The windings are live, and it is not practical to place a conventional thermometer inside them. The winding temperature indicator solves this with the thermal image technique: it measures the oil temperature at the top and adds the heating that the load current produces in the winding relative to the oil.
How the reading is obtained
- A bulb or sensor, in a well in the cover, measures the top oil temperature.
- A current transformer takes a signal proportional to the winding current.
- That signal feeds a heating resistor that surrounds the sensor or acts on the measuring element.
- The sensor temperature rises above the oil temperature in proportion to the current, and this is adjusted to reproduce the typical winding gradient.
The final reading represents the oil temperature plus the heating gradient, that is, an estimate of the hot spot.
What it is used for
- Starting cooling fans or pumps through adjustable contacts.
- Alarm and trip on excessive temperature.
- Recording the maximum temperature reached as an overload reference.
Why calibration matters
The gradient that is programmed comes from the manufacturer’s heat run tests. If the heater setting does not match the transformer, or the current transformer does not match, the reading can be biased high or low. In addition, the indicator responds with the thermal inertia of its own sensor, which is not identical to that of the winding: under rapid load changes, the estimate lags or leads.
Alternatives
Some transformers have fiber optic probes installed in the winding during manufacture. They measure directly at the expected hot spots and are used to validate the thermal image indicator or as the primary measurement.
How to interpret the result
A high winding temperature with normal oil points to high load or internal circulation problems. A high temperature in both oil and winding points to insufficient cooling or overload. It is advisable to compare with the actual load and the ambient temperature before drawing a conclusion.