Energizing current, or inrush, is a transient magnetizing current far above rated current that appears when a transformer is connected and its core saturates, and it can cause protection trips, voltage sags and mechanical stresses.

Why it occurs

In normal operation, the magnetic flux in the core is a sine wave lagging the voltage by about ninety degrees, and the magnetizing current is small. When the breaker closes, the initial flux depends on the instant on the voltage wave at which the connection is made and on the residual flux left by the previous disconnection. If the resulting flux exceeds the saturation value, the core saturates, the inductance drops and the current rises sharply.

The most severe case occurs when closing near the voltage zero crossing, with residual flux in the same direction as the flux being formed: the flux reaches close to twice its normal value plus the residual flux.

What the current looks like

  • Unipolar peaks, sometimes several multiples of rated current, that appear in one direction only during part of the cycle.
  • Strong second harmonic and DC component content.
  • Gradual decay, from fractions of a second to several seconds or more, depending on the circuit resistances and the size of the transformer.

Effects

  • Nuisance tripping of overcurrent and differential protection, if they are not designed to distinguish energization from a fault. Differential relays usually use second-harmonic restraint precisely because of this characteristic.
  • Voltage sags on the network due to the drop across the source impedance, which are noticeable on weak networks.
  • Temporary harmonic distortion and possible excitation of resonances.
  • Mechanical stresses on the windings from the forces associated with high currents.

How it is mitigated

Methods include closing synchronized with the voltage waveform and the residual flux, pre-insertion resistors, or staggered energization of several transformers. In the protection, the harmonic restraint and blocking times are adjusted.

What the engineer sees in practice

A current record with decaying asymmetrical peaks and a temporary voltage drop at the moment of energization. Energizing a transformer in parallel with another already energized one can produce an interaction: the second transformer contributes current that prolongs the transient of the first.

Warning: switching and measurements on energized transformers involve electrical risk and must be carried out by qualified personnel, following the applicable regulations.