24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

Transformers

Clear explanations of concepts, methods, standards and measurements for engineers and technicians.

  • Distribution or power transformer: how do they differ?

    There is no single dividing line: a distribution transformer feeds loads close to the user at lower voltages and with variable operation, while a power transformer interconnects grid voltage levels with greater capacity and more control and protection accessories.

  • Dry-type or oil-immersed transformer?

    An oil-immersed transformer cools better and handles more power and voltage, while a dry-type unit avoids oil and reduces fire risk, but has limits on size and environment.

  • How Do You Connect Two Transformers in Parallel?

    Two transformers can be connected in parallel if they match in voltage, turns ratio, phase displacement (vector group) and phase sequence, and have similar percent impedances so that they share the load properly.

  • How Do You Decide Between Repairing or Replacing an Aging Transformer?

    The decision combines the actual condition of the insulation and the components, the criticality of the unit, the availability of repair and the total cost over the remaining life, not a single test or the age alone.

  • How Do You Diagnose a Transformer After an External Fault Trip?

    First identify which protection operated and what current flowed, then compare electrical, oil and mechanical response tests against reference values to decide whether there was damage before re-energizing.

  • How does a condenser bushing work?

    A condenser bushing distributes electrical stress through concentric conductive layers inside the insulation, forming capacitors in series that maintain a controlled voltage gradient from the conductor to the flange.

  • How Does a Power Transformer Work?

    A power transformer transfers energy between two or more windings by electromagnetic induction: an alternating flux in a magnetic core induces in each winding a voltage proportional to its number of turns.

  • How Is a Polarity Test Performed?

    The polarity test determines whether, at a given instant, the voltage induced in the secondary has the same direction as that of the primary or the opposite; it is done by comparing the voltage between terminals with a low applied voltage, or with a direct current kick.

  • How is a power factor test on a transformer interpreted?

    A power factor test measures the dielectric losses and capacitance of the insulation between windings and to ground; it is interpreted by comparing with previous values and with other phases and similar units, correcting for temperature, and not from an isolated number.

  • How is a sweep frequency response analysis (SFRA) performed?

    Sweep frequency response analysis (SFRA) injects a low-voltage, variable-frequency signal into one transformer terminal and measures the response at another, producing a fingerprint that is compared with references and reveals mechanical deformation.

  • How Is a Transformer Prepared for Out-of-Service Electrical Testing?

    For out-of-service electrical testing, the transformer is de-energized, isolated from all its sources and loads, verified free of voltage and grounded, and the external connections to its bushings are removed, in addition to recording conditions and reference data.

  • How is a transformer vector group verified in the field?

    The vector group is verified in the field by applying a reduced three-phase voltage to the high-voltage side, bonding a high-voltage terminal to a low-voltage terminal and measuring the voltages between the remaining terminals, or with an instrument that directly measures ratio and phase angle.

  • How Is a Transformer Winding Resistance Test Performed?

    The winding resistance test injects direct current into each winding and measures the voltage drop to calculate its resistance, which makes it possible to detect loose connections, broken strands and tap changer problems.

  • How Is an Excitation Current Test Performed?

    The excitation current test applies a reduced alternating voltage to one winding, with the others open, and measures the current flowing in each phase and at each tap changer position in order to compare the pattern with references.

  • How is bushing capacitance measured?

    The capacitance of a condenser-type bushing is measured with a power factor or capacitance instrument, using the test tap, and is compared with the nameplate value and earlier measurements to detect short-circuited layers.

  • How is moisture in a transformer’s solid insulation assessed?

    Moisture in a transformer's solid insulation is assessed indirectly, because almost all the water is in the paper and pressboard and not in the oil: the water content of the oil at a known temperature is combined with equilibrium curves and dielectric measurements.

  • How is residual core magnetization measured?

    The core retains part of the magnetic flux after a disconnection or a direct current test; it is estimated by injecting controlled direct current and integrating the induced voltage, and it is removed by demagnetization.

  • How is tap changer contact resistance measured?

    It is measured by injecting direct current into the winding through the tap changer and recording the voltage drop at each position, in order to compare contact quality across positions and phases.

  • How Is Temporary Overload Capability Determined?

    Temporary overload capability is determined with a thermal model that starts from the prior load, the ambient temperature and the oil and winding time constants; it is limited by the hot spot, aging and the accessories.

  • How is the audible noise level of a transformer measured?

    The audible noise level of a transformer is measured with a sound level meter at points distributed around the unit at a defined distance, with A-weighting, and corrected for background noise to obtain a representative average value.

  • How is the internal temperature of the windings measured?

    The internal temperature of the windings is measured directly with factory-installed fiber optic probes, or estimated with a thermal image indicator or a model that adds to the oil temperature an increment proportional to the load current.

  • How Is the Short-Circuit Impedance Test Performed?

    The short-circuit impedance test shorts the terminals of one winding, applies a reduced voltage to the other until a current close to rated flows, and calculates the impedance from the measured voltage, current and power.

  • How is transformer insulation resistance measured between windings?

    A DC voltage is applied between one winding and another, with the transformer de-energized and disconnected, and the reading is the resistance obtained by dividing that voltage by the small current passing through the insulation.

  • Mineral oil or ester fluid for transformers?

    Mineral oil has decades of experience behind it and costs less; ester fluids offer a higher flash point, biodegradability and better moisture tolerance, with differences in viscosity and in how tests are interpreted.

  • Off-load or on-load tap changer?

    An off-load tap changer is operated only with the transformer de-energized and is used for occasional adjustments; an on-load tap changer changes taps in service and allows continuous voltage regulation, at the cost of greater complexity and maintenance.

  • Stacked core or wound core?

    A stacked core is assembled from cut laminations interleaved at the joints; a wound core is formed from a continuous steel strip, which reduces joints and losses but limits size and ease of assembly with the coils.

  • What Are No-Load and Load Losses in a Transformer?

    No-load losses are those of the core and exist whenever the transformer is energized, almost regardless of the load; load losses are those of the windings plus stray losses, and they grow with the square of the current.

  • What Causes a Trip from Gas Accumulated in the Relay?

    The gas relay trips when gas accumulates in the conservator pipework, either because an internal fault is breaking down the oil or the insulation, or because air has entered the system; gas analysis distinguishes between the two cases.

  • What causes localized heating in the core?

    Localized heating in the core is usually due to abnormal eddy currents: a short circuit between laminations, a double core ground or stray flux in structural parts, and it is detected through thermal gases in the oil.

  • What Does “Tap” Mean on a Transformer?

    A tap is a connection point on a winding that makes it possible to change the number of turns in service and, with it, the transformer's turns ratio.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer