What Is the Vector Group of a Three-Phase Transformer?

The vector group of a three-phase transformer indicates how its windings are connected, in delta, wye or zigzag, and what phase shift results between the high-side and low-side voltages, using a code of letters and a number.

How the designation is read

The group is written with letters and a number, for example Dyn11. Uppercase letters describe the connection of the high-voltage winding and lowercase letters that of the low-voltage winding: D or d for delta, Y or y for wye, and Z or z for zigzag. An n indicates that the neutral is accessible. The number is the phase shift expressed as the hours of a clock: each hour equals thirty degrees, and the high-side voltage is taken as the hand at twelve o’clock.

Why the connection matters

  • Phase shift: once the number is fixed, the relative positions of the voltages on both sides are determined.
  • Zero-sequence currents: the delta allows them to circulate inside the winding, so it isolates the network on one side from ground faults on the other. A wye with a grounded neutral lets them through.
  • Triplen harmonics: the delta traps them in its internal circuit, which limits their propagation through the network.
  • Grounding: the side with a wye and accessible neutral provides a ground reference point and can feed phase-to-neutral loads.
  • Differential protection: the currents on the two sides have a phase shift that the protection must compensate.

What is seen in practice

The nameplate shows the group and the connection diagram. When connecting a new transformer, or replacing an existing one, you must verify that the group matches what is required. Otherwise, unexpected voltages or angles appear between the two sides, and the protection may measure incorrectly.

Parallel operation

Two transformers can operate in parallel only if they have the same phase shift, the same phase sequence and compatible voltage ratios. Connecting them with a different phase shift produces a very high circulating current. Certain groups with different phase shifts can be compatible if the external phases are reconnected, but this is studied carefully before acting.

How it is confirmed

The declared group is verified with a phase shift and transformer ratio test before energizing. Testing and connection of transformers are carried out by qualified personnel in accordance with applicable regulations.