The problem it describes
Nonlinear loads such as switched-mode power supplies, variable-speed drives and rectifiers draw currents with harmonics. Harmonics increase the eddy-current losses in the windings, which grow approximately with the square of the frequency. A transformer carrying a harmonic-rich current runs hotter than with a sinusoidal current of the same RMS value.
Definition
The K-factor is an index of that effect. It is calculated as the sum, over the harmonic orders h, of the relative current of each harmonic squared and multiplied by h squared:
K = Σ (Ih/I)² · h²
where Ih is the current of harmonic order h and I is the total RMS current. For a purely sinusoidal current, the factor equals one; the more harmonics there are and the higher their orders, the higher K is.
K-rated transformer
A K-rated transformer is designed to limit eddy-current losses: it uses subdivided or transposed conductors and other measures, and often a neutral of higher capacity, because in single-phase nonlinear loads the third-harmonic currents add up in the neutral. The rating value indicates the severity of the harmonic profile it was designed for.
What the engineer sees in practice
- A standard transformer feeding nonlinear loads runs hotter than its kVA load suggests, and may require derating.
- Measuring current harmonics makes it possible to calculate the actual K-factor of the load and compare it with that of the transformer.
- The additional losses are concentrated in the windings and the structural parts.
When it does not apply
The K-factor refers to the effect of current harmonics on losses. It does not cover voltage harmonic problems or other effects such as resonance, and it is not the same as other derating factors defined in different standards. A K-rated transformer does not correct harmonics: it only tolerates them.
For selection or derating decisions, use the method in the applicable standard, in its current edition.