Where it sits and why it works
The Buchholz relay is installed in the pipe joining the main tank to the conservator tank, on transformers that have a conservator. Any internal fault that decomposes the oil or the insulation produces gas, and that gas rises toward the conservator, passing through the relay. If the fault is violent, the oil is forced through the same pipe. The relay responds to both phenomena.
Two stages of operation
- Gas alarm: gas collects in the upper part of the housing and lowers the oil level inside the relay; a float activates an alarm contact. This corresponds to incipient faults: overheating, small arcs, discharges.
- Flow trip: a sudden surge of oil toward the conservator pushes a flap or a second element and closes the trip contact. This corresponds to severe faults, such as a high-energy internal arc.
- Low oil level: if oil is lost, the level inside the relay falls and can also activate the contacts.
What to do with the alarm
The accumulated gas can be sampled through a valve for analysis. The first step is to distinguish between air and fault gases: air gets in after work on the oil or through a leak on the suction side of the pumps, and does not indicate damage. Decomposition gases are identified by chromatographic analysis, and their composition points to the type of fault. With a gas alarm, the unit must not be re-energized, and the warning must not be ignored, without investigation.
An example
A transformer gives gas alarms with increasing frequency. Gas sampling and dissolved gas analysis show hydrocarbons and not just air: this points to a real thermal or electrical fault. If, on the other hand, the alarm appears right after oil filling and the gas is almost entirely air, it is bled off and monitored.
When it does not apply
Sealed transformers without a conservator do not have a Buchholz relay; they use other protections, such as sudden pressure relays and pressure relief devices. In addition, the Buchholz relay does not detect faults that generate neither gas nor oil movement, which is why it complements differential protection and does not replace it.
Warning: gas sampling on energized equipment involves electrical risk; it must be done by qualified personnel, according to the applicable regulations and procedures.