What it is
In an ideal transformer, all the flux created by one winding links the other. In a real one, part of the flux closes through the air, the oil or the structural parts, without passing through the core or linking both windings. That part is the leakage flux.
Electrical consequences
- Leakage reactance: leakage flux behaves like an inductance in series with each winding. It is the main component of the transformer’s short-circuit impedance.
- Fault current limiting: the impedance limits the current during a short circuit. A higher impedance limits it more, but also increases the voltage drop under load.
- Regulation: the voltage drop between no load and load depends largely on that reactance.
Physical consequences
- Forces on the windings: the interaction between the current and the leakage flux produces radial and axial forces proportional to the square of the current. In a short circuit they are very large, and the design must withstand them.
- Additional losses: stray flux induces currents in the tank, the flanges, the beams and the conductors themselves, causing localized heating. These losses are mitigated with magnetic or conductive shields and with subdivided conductors.
How it is used for diagnostics
Measuring the short-circuit reactance or impedance in the field and comparing it with the nameplate or with earlier measurements is a mechanical diagnostic technique. If the windings shift or deform, the geometry that determines the leakage flux changes, and so does the measurement. This is one of the reasons it is measured after a short-circuit event. Frequency response (SFRA) also depends on this geometry.
An example
After a trip caused by an external fault, the leakage reactance of one phase measured in the field turns out to differ from that of the other two and from the previous value. That difference suggests winding displacement, which must be confirmed with other tests.
What not to confuse it with
It must not be mixed up with excitation current, which relates to the main flux in the core. Leakage flux depends on the load current; the main flux depends on the voltage.