24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

Technical guides

Clear explanations of concepts, methods, standards and measurements for engineers and technicians.

  • How is gain determined by comparison?

    The received signal is measured with an antenna of known gain and then with the antenna under test, in the same geometry. The difference in decibels between the two readings, added to the gain of the reference, gives the gain of the antenna under test.

  • How is grid frequency variation measured?

    Grid frequency variation is measured by counting the cycles of the fundamental voltage over a defined time window and comparing the result with the nominal value. Frequency reflects the balance between generation and load in the system.

  • How is immunity to radiated fields measured?

    A uniform, modulated electromagnetic field is generated with an antenna and an amplifier and swept in frequency over the equipment, while observing whether its operation stays within the defined performance criterion. The field strength is calibrated beforehand with a probe in the test area.

  • How is inhibitor content measured?

    Inhibitor content in oil is normally determined by infrared spectroscopy, measuring the characteristic absorption of the antioxidant's phenolic group, or by chromatographic methods that separate and quantify the additive.

  • How is irradiance measured with a pyranometer?

    A pyranometer measures global irradiance by measuring solar radiation on a flat surface; for the reading to be valid, it must be clean, level or aligned with the plane of interest, free of shade and within its calibration period.

  • How Is Leakage Current Measured During a DC Test?

    Leakage current in a DC test is measured with a microammeter at the source and interpreted by separating capacitive charging, absorption and conduction, the component that reveals the condition of the insulation.

  • How is leakage current measured in portable equipment?

    Leakage current in portable equipment is measured with the equipment connected and running under controlled conditions, using an instrument that records the current flowing to ground or to accessible parts, to confirm that it poses no risk to the user.

  • How is level measured with a hydrostatic sensor?

    A hydrostatic sensor measures level because the pressure at the bottom of a liquid is proportional to its height and density; with the density and gravity known, the measured pressure is converted into liquid height.

  • How Is Linearity Determined?

    Linearity is determined by measuring the instrument's response at several points across the span, fitting a reference line to the data and calculating the maximum deviation of the points from that line.

  • How is load estimated during an inspection?

    Load during an inspection is estimated by measuring the current flowing at the time of the shot or by reading the panel instruments, and comparing it with the rated current of the circuit.

  • How Is Long-Term Drift Determined?

    Long-term drift is determined by comparing the results of successive calibrations of the same instrument over time and analyzing how the error at each point changes from one calibration to the next.

  • How is metrology managed on a production line?

    On a production line, metrology is managed by identifying which product characteristics depend on a measurement, ensuring that each measurement is capable enough for its tolerance, and continuously verifying that it remains so.

  • How is moisture in a transformer’s solid insulation assessed?

    Moisture in a transformer's solid insulation is assessed indirectly, because almost all the water is in the paper and pressboard and not in the oil: the water content of the oil at a known temperature is combined with equilibrium curves and dielectric measurements.

  • How Is Motor Starting Current Measured?

    Motor starting current is measured by recording the current throughout the entire start with an instrument capable of capturing the initial peak and the decay, not with an averaged reading.

  • How Is Motor Winding Resistance Measured?

    The winding resistance of a motor is measured with the motor de-energized and cold, using a four-wire low-resistance instrument, phase to phase, and is corrected for temperature before comparing.

  • How is neutral-to-ground voltage recorded?

    Neutral-to-ground voltage is recorded by connecting one of the analyzer's voltage channels between the two points and logging its RMS value and waveform over a representative period, always together with the neutral current.

  • How is newly received oil validated?

    New oil is validated by comparing its documentation with what was ordered, inspecting containers and seals, and testing a representative sample against the purchase specifications before filling the equipment.

  • How is noise figure measured with the Y-factor method?

    In the Y-factor method, a calibrated noise source is connected to the input of the device, first off and then on, and the increase in noise power at the output is measured; the noise figure is obtained from that ratio and the excess noise of the source.

  • How Is Oil Dehydrated in the Field?

    Oil is dehydrated in the field by circulating it through a unit that heats it moderately and exposes it to vacuum to evaporate the water; however, most of the water is in the paper, so complete drying is slow.

  • How Is Oil Filtered and Degassed Under Vacuum?

    To filter and degas oil under vacuum, the liquid is circulated through filters and a low-pressure chamber where water and dissolved gases come out of solution, while moderate heating aids the process.

  • How is oil viscosity measured?

    The viscosity of an insulating oil is measured with a capillary viscometer: the time a fixed volume takes to flow by gravity through a calibrated tube, in a bath held at a stable temperature, is measured and multiplied by the instrument constant.

  • How is oil with polychlorinated biphenyls handled?

    Oil containing polychlorinated biphenyls (PCBs) is handled as hazardous material: it is identified by analysis, segregated without being mixed, and managed through authorized channels according to the applicable regulations.

  • How is oxygen measured in a confined space?

    Oxygen in a confined space is measured with the oxygen sensor of a calibrated detector, from outside before entry and then at several levels, letting the reading stabilize and keeping measurement continuous during the work.

  • How is particle content measured?

    Particle content in oil is measured with an automatic counter that passes the oil between a light source and a detector and counts and sorts the particles by size according to the light they block, or it is determined by filtration and microscope counting.

  • How Is Phase Rotation Verified?

    Phase rotation is verified with a phase sequence meter connected to the three phases, which indicates whether the sequence is forward or reverse; the motor's direction of rotation is then confirmed and, if necessary, two phases are swapped with everything de-energized.

  • How Is Power Quality Compliance Verified at the Point of Interconnection?

    To verify power quality at the point of interconnection, measure there with a standardized method over a representative period and compare the statistical results with the criteria that apply under the contract, the regulation or the chosen standard.

  • How Is Power Quality Data Aggregated into Averaging Intervals?

    Power quality data is aggregated by calculating a base quantity over short windows and combining those values, usually by root mean square, into longer intervals; minimums, maximums and events are recorded separately so that the average does not hide them.

  • How is power quality validated after installing a variable speed drive?

    Power quality is validated by comparing measurements taken before and after installing the drive, at the point of coupling and at different load levels, against the applicable criteria.

  • How is PPE inspected before use?

    Personal protective equipment is inspected before each use by comparing its condition with what its function demands: look for visible damage, contamination, deformation or expired service life, and remove anything doubtful from service.

  • How is preventive maintenance of a solar array carried out?

    Preventive maintenance of a solar array combines visual inspections, cleaning according to soiling, checks of connections and structures, periodic electrical tests and tracking of monitoring data, under a program defined by the plant.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer