24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How is power quality validated after installing a variable speed drive?

Power quality is validated by comparing measurements taken before and after installing the drive, at the point of coupling and at different load levels, against the applicable criteria.

Why validation is needed

A drive is a nonlinear load: it draws current in pulses through its rectifier and therefore injects harmonics into the grid. How much this matters depends on the drive’s power relative to the capacity of the grid and on the other loads. Validation confirms that the new installation does not degrade the voltage seen by other equipment or exceed what the regulations or the utility allow.

What is measured

  • Current and voltage harmonic distortion, by harmonic order, not just the total value.
  • Power factor and reactive power.
  • Voltage unbalance and current unbalance.
  • Sags and transients during starting and operation.
  • DC bus voltage if the drive reports it, as an indicator of equipment health.

Procedure

  1. Record the prior condition at the point of common coupling, with the plant operating normally. This is the baseline.
  2. After installation, record again at the same point and for an equivalent duration.
  3. Vary the drive load. Relative current distortion is usually higher at low load, while the effect on voltage depends on the absolute current.
  4. Also measure at the drive input to distinguish its own contribution from what the grid was already carrying.
  5. Compare with the criteria of the applicable harmonics standard, in its current edition, and with those of the utility.

What to look for

If there are capacitor banks in the installation, check that they do not form a resonance with the grid inductance at any harmonic frequency excited by the drive; it shows up as amplification of a harmonic and as overheating or capacitor failures. It is also verified that the drive does not trip because of pre-existing grid distortion and that other sensitive equipment is not affected.

What to do with the result

If the values exceed the criteria, options include line or DC reactors, passive or active filters, or drives with higher-pulse or active rectifiers. Measurements on energized equipment, and the handling of drives with charged capacitors, are for qualified personnel.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer