24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How Is Motor Starting Current Measured?

Motor starting current is measured by recording the current throughout the entire start with an instrument capable of capturing the initial peak and the decay, not with an averaged reading.

What happens during a start

When an induction motor is connected at full voltage, the rotor is at a standstill and the motor behaves like a transformer with a short-circuited secondary. The initial current is several times the rated current and decreases as the rotor accelerates and approaches its speed. During the first few cycles there may also be a decaying unidirectional component that depends on the instant of closing.

How it is measured

  • Instrument: an analyzer or recorder with sufficient sampling and the ability to capture the RMS value cycle by cycle, or a clamp meter with an inrush current function. An ordinary multimeter averages over a longer time and underestimates the peak.
  • Sensor: a current clamp or probe with enough range for the peak, without saturating. If the current exceeds the range, the measurement is clipped.
  • Setup: activate recording before the start with a current threshold trigger, so that the entire evolution is recorded.
  • Voltage: also measure the voltage at the terminals during the start, because the voltage drop caused by the current affects acceleration.

What data is obtained

The initial peak, the RMS value in the first cycles, the time until the current falls to the operating value and the shape of the curve. These data are compared with what the nameplate indicates and with what the system can accept without tripping protective devices or causing unacceptable voltage sags.

How to interpret the result

A start that lasts longer than expected indicates a load that resists acceleration, low voltage or a problem in the motor. An initial current much higher than expected may be due to the motor being of a different design class than assumed. If there is a soft starter or a drive, the current waveform is very different from that of a direct-on-line start, and the measurement verifies its ramps and limits.

Common mistakes

  • Using a slow instrument that displays an averaged value.
  • Starting the recording after the motor has started.
  • Choosing a current range that saturates with the peak.
  • Measuring without the associated voltage.

Clamps are placed in energized panels, a task for qualified personnel with suitable protective equipment.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer