Where the water is
In a transformer, water is distributed between the oil and the cellulose, with the great majority held in the paper and pressboard. The equilibrium depends on temperature: on heating, some of the water passes from the paper to the oil; on cooling, it returns. That is why drying only the oil is not enough, and why the water content of the oil must be interpreted together with its temperature.
How it is done
- Vacuum dehydration: a mobile unit pumps the oil through heaters and a vacuum chamber where it is dispersed as a film or droplets. The water evaporates at low temperature and is removed by condensation or through the vacuum system.
- Centrifuging or coalescence: these remove free and emulsified water, but not dissolved water.
- Absorbent filters: these retain water in small quantities.
Drying the paper
To reduce the moisture in the solid insulation, hot oil must be recirculated for long periods, or processes using vacuum in the tank or hot oil spray must be applied. Water migrates slowly from the cellulose to the oil, and what is measured in the oil at the end can rise again as it stabilizes.
What an engineer sees in practice
The water content of the oil falls quickly at first and then stalls because the paper replenishes it. An apparently dry oil can show moisture again weeks later. The process is tracked with periodic measurements of water in oil and, when possible, with an estimate of the water content in the paper.
How to tell whether it worked
Compare the moisture in the oil at a comparable temperature before and after, and repeat the measurement after a rest period. Work with the transformer open or connected to a process unit must be carried out by qualified personnel, with the equipment de-energized and the applicable safety procedures in place.