What is being sought
The inhibitor is the antioxidant that protects the oil, normally a hindered phenol such as DBPC. Measuring how much remains shows how much life margin the oil has before its oxidation accelerates, and helps decide whether it should be replenished.
Infrared spectroscopy
Molecules absorb infrared light at wavelengths characteristic of their bonds. The hydroxyl group of the phenol has its own band. The absorbance of that band in the oil is measured and compared with a calibration curve prepared from oils with known concentrations of the same additive. The method is fast and requires little preparation, but it must be calibrated with a similar base oil, because other components can interfere, and it is sensitive to water and to oxidized compounds that absorb in the nearby region.
Chromatographic methods
Liquid or gas chromatography separates the inhibitor from the other components and quantifies it with a detector. It is more selective and is useful when several additives are present or when infrared is affected by interference, although it demands more time and equipment.
What an engineer sees in practice
The report gives the concentration, usually as a percentage by mass or in parts per million. It is compared with the original concentration of the oil and with previous samples. A steady decline makes it possible to estimate when the inhibitor will be depleted.
How to use the data
- Confirm the type of inhibitor, because not all of them are measured with the same method.
- Build the trend using the same method every time.
- Cross-check against acidity, interfacial tension, and color.
- Decide on replenishment if the oil is still in good condition, or on reclamation and replenishment if it is already degraded.
Low acidity must not be confused with sufficient inhibitor: the oil may be on the verge of oxidizing if the inhibitor has already been consumed.