What phase sequence is
In a three-phase system, the voltages reach their maximum in a given order: A, B, C in the forward sequence, or A, C, B in the reverse sequence. That order determines which way the magnetic field of a three-phase motor rotates. With the sequence reversed, the motor runs backward, which in pumps, compressors, fans or conveyor belts can cause damage or poor operation.
How it is verified
- Phase sequence meter or phase sequence indicator: it is connected to the three phases and shows, with lights or a rotating disc, whether the sequence is forward or reverse relative to the one marked on the instrument. It is the most direct method and is done before connecting the motor.
- Phase measurement with an analyzer or oscilloscope: this makes it possible to see the order of the zero crossings between the voltages.
- Motor rotation test: with the coupling disconnected, or with a load that will not be damaged by reverse rotation, the motor is bumped briefly and the direction is observed on the fan or shaft.
When it is corrected
If the sequence is the opposite of what is required, two of the three phases are swapped at a chosen connection point, always with the circuit de-energized, locked out and verified dead. On a motor fed by a drive, the direction is usually changed with a parameter or a reverse command on the equipment, without moving power cables.
Phase rotation and phasing are not the same
Rotation indicates the order of the phases. Phasing, necessary before connecting two sources or two transformers in parallel, checks that each phase of one source matches the corresponding phase of the other in voltage and angle. Two systems can have the same sequence and still be out of phase, for example because of the transformer connections.
Common mistakes
- Assuming that conductor colors guarantee the sequence.
- Swapping phases at the motor without verifying that other motors on the same panel require the same sequence.
- Confusing the instrument indication with the motor sequence without considering its connection.
- Changing the phase order in a system with metering or directional protection without reviewing the effect.
These checks are made on circuits with hazardous voltage; they must be carried out by qualified personnel in accordance with applicable regulations.