How Is Oil Filtered and Degassed Under Vacuum?

To filter and degas oil under vacuum, the liquid is circulated through filters and a low-pressure chamber where water and dissolved gases come out of solution, while moderate heating aids the process.

Physical principle

The amount of gas a liquid keeps dissolved is proportional to the partial pressure of that gas above it. If the pressure above the oil is lowered substantially, dissolved gases and water come out of solution and are evacuated. Increasing the exposed surface (thin film, droplets, column packing) and heating moderately speeds up the transfer.

Stages of a typical unit

  1. Inlet and prefilter: retains coarse particles to protect the pump.
  2. Heating: raises the temperature as needed to lower the viscosity and promote evaporation, without overheating the oil.
  3. Vacuum chamber: the oil is spread over a large surface; water and gases pass into the vapor phase.
  4. Vacuum system and condenser: extracts the gases and condenses the water.
  5. Fine filters: remove particles before the oil is returned.

What to control

  • Oil temperature: excessive heat degrades the oil and can carry off some of the volatile additives.
  • Vacuum level and tightness of hoses and connections, so that no air or moisture enters.
  • Pressure drop across filters, which indicates saturation.
  • Flow and recirculation, until analyses confirm the result.

What an engineer sees in practice

The oil volume is recirculated several times, and water, gases and particles are measured at intervals. If the value stops improving, the remaining water is probably coming from the paper, not from the oil.

When it does not apply

The process does not regenerate an oxidized oil, does not remove acids or sludge and does not correct degraded paper. Nor does it replace a review of the cause of the contamination. Connections to the transformer and operation of the unit must be carried out by qualified personnel, with the equipment de-energized.