The problem of passing through a grounded wall
A bushing carries a high-voltage conductor through the tank cover, which is grounded. Unaided, the electric field would concentrate at the edge of the flange and along the surface, with a risk of discharges. The condenser design solves this by controlling how the voltage is distributed inside the insulation.
Operating principle
Insulating paper or an equivalent material is wound around the center conductor, interleaved with concentric conductive foils of decreasing length. Each pair of adjacent foils forms a capacitor, and the assembly is a chain of capacitors in series. The voltage divides among them almost uniformly in the radial direction, and the different foil lengths make the distribution more uniform along the axis as well. The result is a controlled field, with no peaks at the end.
Insulation variants
- Oil-impregnated paper.
- Resin-impregnated paper.
- Paper or fiber with solid resin, with no internal oil.
Sensitivity to moisture and behavior in the event of leaks change, but the capacitive principle is the same.
The test tap
In many bushings, the outermost foil is connected to an accessible tap near the flange. This tap makes it possible to measure the capacitance and dissipation factor (tan delta) of the main insulation without removing the bushing. Changes in capacitance may indicate a short circuit between layers; an increase in tan delta suggests moisture or insulation deterioration.
In service, this tap must remain connected to ground or to its protective cover. If it is left open, a high voltage appears at that point and a discharge or bushing failure can occur.
What to check first
- Oil level and appearance, on models with a sight glass.
- Condition of the porcelain or the external composite insulator.
- Test tap cover in place.
- Capacitance and tan delta history against the nameplate and earlier measurements.
Condenser bushings are critical components: their failure can be violent and cause a transformer fire.
Warning: work on bushings and measurements at their tap involve high voltage. They must be carried out by qualified personnel in accordance with the applicable regulations and safety procedures.