24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How Is a Polarity Test Performed?

The polarity test determines whether, at a given instant, the voltage induced in the secondary has the same direction as that of the primary or the opposite; it is done by comparing the voltage between terminals with a low applied voltage, or with a direct current kick.

What is determined

Winding terminals are marked to indicate which ends have the same instantaneous voltage direction. If they are connected incorrectly when paralleling transformers or connecting protection and meters, the result is a voltage opposite to the one expected. The test confirms that the marking is correct. In a single-phase transformer, polarity is classed as subtractive or additive.

AC voltage method

  1. Join one terminal of the high-voltage winding to the adjacent terminal of the low-voltage winding, for example those marked 1 on both.
  2. Apply a reduced, safe alternating voltage to the high-voltage winding.
  3. Measure the applied voltage and the voltage between the other two free terminals.

If the voltage measured between the free terminals is lower than the applied voltage, the polarity is subtractive. If it is higher, it is additive. This happens because, with the jumper in place, the primary and secondary voltages subtract or add in the loop.

DC kick method

A low-voltage DC source, such as a battery, is connected to the high-voltage winding, and a sensitive needle instrument to the low-voltage winding. When the circuit is closed, the initial deflection of the instrument indicates the relative direction: if it goes to one side, the polarity is of one type; to the other side, of the opposite type. On opening, the deflection reverses. A clear connection and reference criterion are needed, because the interpretation depends on the polarities of the instrument.

Precautions

  • Apply only the reduced voltage indicated by the procedure, never rated voltage.
  • Open the DC circuit with care: interrupting the current in a coil induces a high voltage.
  • Disconnect loads and external connections, and demagnetize if necessary after using direct current.

Common mistakes

  • Joining the wrong terminals and reaching the opposite conclusion.
  • Reading a small noise or induced voltage as if it were the result.
  • Leaving the battery connected for too long.
  • Extrapolating single-phase polarity to a three-phase transformer without considering its vector group.

How to interpret the result

The result is compared with the nameplate marking. A discrepancy means the internal connections, the bushing markings or the diagram must be reviewed. When the unit is tested with a transformer turns ratio meter, it usually determines polarity in the same measurement.

The test requires qualified personnel and a transformer that is de-energized and isolated from the network.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer