What is really being measured
Tap changer contact resistance is not measured in isolation. What you obtain is the winding resistance at each position, which includes the conductor, the connections, and the contacts of the selector and the diverter switch. A deteriorated contact adds resistance to that path, which is why it appears as a difference between positions.
Measurement method
- With the transformer de-energized, isolated and grounded according to the procedure, the current and voltage leads are connected separately (four-wire or Kelvin method) so that the resistance of the test leads does not enter the reading.
- A stable direct current is injected. The winding is a large inductance, so the reading takes time to stabilize; measuring before the current settles gives false values.
- The resistance is recorded at each tap changer position, phase by phase, and the winding temperature is noted.
- When finished, the energy stored in the inductance is discharged before the leads are disconnected.
Dynamic measurement
On on-load tap changers there is also dynamic resistance measurement: the direct current is recorded while the tap changer moves from one position to another. The waveform shows how the contacts and transition resistors act during the change, information a static reading does not provide, such as momentary interruptions or abnormal transitions.
How to interpret the result
- Trend across positions: the resistance should vary regularly from one position to the next. An isolated jump points to a suspect contact or connection.
- Comparison between phases: at equivalent positions, the three phases should behave similarly.
- History: comparison with earlier measurements on the same equipment, corrected for temperature, is more reliable than any absolute value.
A tap changer with coking or contact wear usually shows readings that become erratic or fluctuate. If the reading wanders without stabilizing, suspect the contact and not only the instrumentation.
When it is not enough
Resistance measurement detects conduction problems, but it does not reveal the full mechanical state of the mechanism or the condition of the compartment oil. It is complemented by inspection, dissolved gas analysis and operating time tests.
Warning: these tests involve high-voltage equipment and stored energy. They must be performed only by qualified personnel, following the applicable regulations and safety procedures.