How is bushing capacitance measured?

The capacitance of a condenser-type bushing is measured with a power factor or capacitance instrument, using the test tap, and is compared with the nameplate value and earlier measurements to detect short-circuited layers.

Why it is measured

A high-voltage condenser-type bushing contains concentric conductive layers separated by insulation, which distribute the electric field evenly. This structure behaves like a chain of capacitors in series. If the insulation between some layers fails and they short-circuit, the total capacitance increases and the remaining layers carry more stress, until the bushing fails violently. Capacitance is a sensitive indicator of this condition.

What is measured

  • C1: the capacitance between the center conductor and the test tap, that is, the main part of the insulation.
  • C2: the capacitance between the test tap and the grounded flange.

The dissipation factor or power factor, which gives information on dielectric losses, is normally measured as well.

How it is measured

  1. With the transformer de-energized and the bushing disconnected from the bus, the porcelain or external surface is cleaned.
  2. The test tap cover is opened and the instrument is connected to the tap, in a mode that measures the capacitance between the center conductor and the tap, with the flange grounded.
  3. An AC test voltage is applied, at the level the procedure and the tap allow, and capacitance and dissipation factor are recorded.
  4. To measure C2, the corresponding configuration is used, generally with a lower voltage.
  5. On bushings without a test tap, methods such as a hot collar on the porcelain are used, with less accuracy.

Special precautions

The test tap cover must be reinstalled when finished. A tap left open or ungrounded in operation can reach a dangerous voltage and cause a failure. Results are also corrected for temperature when the procedure calls for it.

Common mistakes

  • Measuring with wet or dirty surfaces, which add leakage.
  • Leaving other devices connected to the conductor.
  • Forgetting the test tap cover.
  • Comparing values from bushings of different models.

How to interpret the result

The result is compared with the nameplate and with earlier campaigns. An increase in capacitance relative to the reference suggests short-circuited layers; a decrease suggests loss of contact or the presence of gas. A high dissipation factor indicates moisture or degradation. Acceptance criteria are defined by the standard or the manufacturer. Work is done by qualified personnel, with the equipment de-energized.