What makes the core heat up
A core always has hysteresis and eddy current losses, and they are evenly distributed. Localized heating is something else: one region concentrates losses because an unintended current or flux path passes through it.
Main causes
- Short circuit between laminations: the insulation between laminations is damaged by cutting burrs, impacts, corrosion or contamination. Eddy current circulates between laminations and heats that area.
- Double core ground: the core must be grounded at a single point. If there are two, a loop forms in which stray flux induces a circulating current that heats the connections and the core.
- Stray flux in structures: in beams, flanges, bolts and parts of the tank near the windings, stray flux induces currents that heat those parts, especially if the shielding or screens are inadequate.
- Uninsulated core bolts or metal bridges: these can join laminations or create closed loops.
How it shows up
- Thermal fault gases in dissolved gas analysis, with a predominance of thermal-fault hydrocarbons and their relationship to the temperature reached.
- A rise in oil temperature without an equivalent change in load.
- Abnormal current measured in the core ground conductor.
- Darkened oil, or oil containing carbon, in advanced cases.
How it is investigated
- The dissolved gas trend is reviewed to see whether the pattern is thermal and sustained.
- The current in the core ground connection is measured, if accessible.
- With the equipment out of service, the insulation resistance from the core to the tank is measured to detect additional grounds.
- If the result warrants it, the core is inspected internally.
How to interpret the result
A low-temperature thermal fault can remain stable for years, and a high-temperature one can be destructive. What is decisive is the gas trend, not an isolated reading.
Warning: measurements on energized equipment and internal inspection must be carried out by qualified personnel, in accordance with the applicable regulations.