What Are No-Load and Load Losses in a Transformer?

No-load losses are those of the core and exist whenever the transformer is energized, almost regardless of the load; load losses are those of the windings plus stray losses, and they grow with the square of the current.

Two sources of losses with different behavior

The energy a transformer does not deliver turns into heat. These losses are separated into two groups because they depend on different variables.

No-load losses (core)

They occur in the magnetic material as it is alternately magnetized. They include hysteresis and the eddy currents induced in the laminations. They depend on the applied voltage and the frequency, and since the voltage is usually practically constant, they are almost constant throughout the time the transformer is energized, whether or not there is load. They are reduced with better-quality steel, thinner laminations and better core design.

Load losses (windings)

They come mainly from the resistance of the conductors: the heat is the resistance times the square of the current. Added to these are additional losses from stray flux that induces currents in conductors, tank and structure. If the load doubles, these losses are multiplied by four, and since resistance increases with temperature, values are referred to a reference temperature.

How they are measured

  • The no-load test feeds one winding at rated voltage with the others open and measures the power absorbed.
  • The short-circuit test short-circuits one winding, feeds the other with rated current and measures the power absorbed.

What it means for the user

Since no-load losses never stop, a lightly loaded transformer spends a large share of its energy in the core; in a heavily loaded one, heat in the windings dominates. Maximum efficiency is reached when variable losses equal fixed losses, which happens at a partial load that depends on the design. That is why the typical load level matters when choosing between alternatives with different costs and losses.

Common mistakes

  • Comparing the losses of two transformers without the same conditions and reference temperatures.
  • Adding losses without weighting them by actual load time.
  • Considering winding heat to be the only relevant loss.
  • Ignoring the effect of harmonics, which raise eddy-current losses under load.

The total cost of a transformer over its life includes the value of the energy lost, not just its purchase price.