The gas comes from two sources
Gas collects in the relay because it rises through the pipework toward the conservator. What matters is where that gas comes from.
Possible causes
- Internal fault: an arc, a discharge or a hot spot breaks down the oil and the cellulose and generates combustible gases such as hydrogen and hydrocarbons, plus carbon monoxide and carbon dioxide if paper is involved.
- Trapped air: after oil filling, work on the unit or a leak repair, air remains in radiators, bushings or pipework and escapes through the relay. Air can also enter through a leak on the suction side of a pump.
- Release of dissolved gas: a sudden drop in temperature or pressure can release dissolved gases.
- Oil loss: if the level falls, the relay fills with air or with gas from the tank and can operate its contacts.
- Spurious trip: vibration, an earthquake or a contact problem can move the floats.
How to tell them apart
- Record which contact operated: gas alarm or trip.
- Take a sample of the gas from the relay through its valve and analyze it. The presence of combustible gases and their proportions point to the type of fault; a gas that is only air points to another cause.
- Take an oil sample for dissolved gas analysis and compare it with earlier samples.
- Perform supporting electrical tests, such as transformer turns ratio, winding resistance and excitation current, to look for damage.
How to interpret the result
Fault gases in the relay and in the oil, with a consistent composition, indicate that the transformer has a real defect and must not return to service until it has been explained. If the gas is air and the oil analyses do not change, the cause was trapped air, and the unit is monitored for any recurrence.
When it does not apply
This concerns only transformers with a conservator and a relay. In sealed units, other pressure devices are the equivalent.
Warning: sampling and testing on a transformer that has tripped involve electrical hazards and the risk of flammable gases. They must be performed by qualified personnel, in accordance with applicable regulations.