Why they are used on busbars
Busbars in panels and substations are usually thick, irregular in shape and short on space, which makes a rigid clamp hard to use. A flexible coil surrounds the conductor regardless of its shape, and because it has no magnetic core it does not saturate with high currents or with a small DC component. In addition, a single sensor covers a very wide current range.
How it is placed
- Choose the right coil length so that it goes around the busbar without being forced.
- Follow the arrow marked on the coil, which indicates the direction of current so that the sign of the power is correct.
- Close the coupling properly. The joint is part of the winding; if it is poorly closed or dirty, an error appears.
- Keep the circular shape as regular as possible and the busbar centered, avoiding tight bends.
- Connect to the integrator or to the analyzer input with the correct scale factor for the selected range.
What affects accuracy
A flexible coil is sensitive to the position of the conductor inside the loop and to the fields of neighboring conductors, especially when the phases of a busbar are very close to each other. These effects are smaller with longer, well-closed coils. An integrator with low-frequency error or drift can shift the measurement. At small currents the signal is weak and there is more noise.
What an engineer sees in practice
If the readings look strange, for example phase currents very different from those expected or power with the opposite sign, the most common causes are a reversed arrow, a poorly closed coil or another phase too close by. A useful check is to compare the reading with another independent measurement, such as a panel meter.
Safety
Installing a coil on energized busbars involves arc flash and contact hazards. It must be done by qualified personnel, with the protective equipment and procedures required by applicable regulations, and after verifying that the coil insulation is suitable for the voltage level of the conductor.