24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How does power quality analysis help reduce Joule losses?

Power quality analysis reduces Joule losses by revealing the currents that do no useful work, such as harmonics, reactive current, and unbalance, which raise the RMS value of the current and with it the heating.

The principle

The power lost in a conductor is proportional to the square of the RMS current flowing through it and to its resistance. Anything that increases the RMS current without increasing useful work increases losses. A power quality analysis identifies the current components that only produce heat.

Sources of current that do no useful work

  • Reactive power: with a low power factor, the line current is higher for the same active power. That additional current heats cables and transformers.
  • Harmonics: distorted current has an RMS value higher than its fundamental component. In addition, the effective resistance of the conductor grows with frequency because of the skin effect, and additional eddy-current losses appear in transformers.
  • Phase unbalance: the most heavily loaded phase loses more than the less loaded phases save, because losses depend on the square.
  • Neutral current: triplen harmonics from single-phase loads add in the neutral and heat it.
  • Poor connections: high contact resistance concentrates losses at one point.

What the analysis provides

An analyzer records current per phase and in the neutral, power factor, distortion, and unbalance over a complete operating cycle. From this, the loss profile is built and the dominant contributions are identified. Losses can be estimated from the conductor resistance and the measured RMS current, and scenarios can be compared: with and without compensation, with redistributed load, with a filter.

Actions that usually follow

  1. Correct the power factor, taking care that the capacitors do not enter into resonance with the harmonics.
  2. Redistribute single-phase loads among phases.
  3. Install filters or reactors where distortion is the dominant cause.
  4. Review conductor cross-sections and connections on the most heavily loaded sections.

How to interpret the result

It is best to prioritize by energy lost over time, not by the highest instantaneous value, and to assess whether the investment pays for itself through the energy recovered and the lower operating temperature. Measurements in energized panels must be made by qualified personnel following the applicable regulations.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer