Principle
An inductance and a capacitor in series have a frequency at which their reactances cancel and the impedance of the pair is at its minimum, limited by the resistance. If that frequency matches a harmonic, the filter, connected in parallel with the load, offers that current a lower-impedance path than the grid does. Most of the harmonic current then flows through the filter rather than through the source.
General design steps
- Measure. Obtain the load current spectrum and the short-circuit power at the point. Without these there is no design basis.
- Choose the harmonics to filter. The usual starting point is the lowest harmonic with the highest amplitude, such as the fifth in loads with six-pulse rectifiers, and branches are added for the next one if needed.
- Define the reactive power. The filter capacitor supplies fundamental reactive power, which must stay within what the installation can absorb without being overcompensated.
- Tune slightly below the harmonic. Component tolerance, aging and temperature shift the tuning, and tuning above the harmonic would put the filter at risk.
- Verify ratings. The capacitor and inductor must withstand the fundamental current plus the harmonics, the resulting voltage and the heating.
The side effect that must be checked
Together with the grid impedance, a tuned filter creates a parallel resonance at a frequency below the tuned frequency. If another harmonic or an interharmonic is present there, it is amplified. That is why the design includes a frequency-impedance study of the grid with the filter, and why branches or a damped high-pass filter are sometimes added.
Common mistakes
- Designing with the nameplate current instead of the measured spectrum.
- Ignoring changes in grid configuration, which alter the source impedance.
- Installing the filter without checking that it will not overload by absorbing harmonics from other nearby loads.
- Failing to provide capacitor protection and safe discharge.
Work on this equipment must be carried out by qualified personnel in accordance with applicable regulations.