Step 1: how many kvar
Start from the active power P measured during the period of highest demand, the present power factor and the target. The reactive power to compensate is Q = P · (tan φ1 − tan φ2), where φ1 is the present angle and φ2 the desired one. Use an actual load record, not the nameplate power of the equipment, because motors rarely operate at full load.
Step 2: where the resonance falls
The capacitor and the source inductance (transformer and network) form a resonant circuit as seen from the harmonic-producing loads. A common estimate of the resonant harmonic order is the square root of the ratio of the short-circuit power at the point to the bank power. If that order approaches a harmonic that is present, such as the fifth or seventh in facilities with rectifiers, harmonic currents and voltages are amplified. This calculation is only an estimate and must be made with actual network data.
Step 3: decide the configuration
- No significant harmonics: standard banks may be acceptable, still verifying the resonance.
- With harmonics: capacitors with series reactors, tuned below the lowest significant harmonic, so that the assembly behaves inductively at those frequencies and does not resonate with the network.
- High distortion: a tuned filter or an active filter, evaluated together.
The rated voltage of the capacitors must be higher when there are series reactors or elevated voltage, and the total harmonic current must be within their capacity.
Step 4: stages
If the load varies, the bank is divided into stages controlled by a regulator, to avoid overcompensation at low load. Each stage needs contactors suited to capacitive switching and a discharge time before reconnection.
What to check first
Before choosing, measure current and voltage harmonics with the bank disconnected. A design based only on power factor ignores precisely the main risk. Installation and commissioning are work for qualified personnel, because capacitors store a dangerous charge.