First, what do you want to know?
The same analyzer connected in three different places tells three different stories. The harmonic current of a load does not look the same at the service entrance, where it adds to that of the other loads, as on that load’s own feeder. Nor is the voltage the same at the service entrance as at the end of a long feeder.
Options and what they are for
- Service entrance or point of interconnection: answers whether the facility, as seen from the network, meets the applicable criteria and how much it contributes or receives overall.
- Affected load feeder: shows what the failing equipment actually receives, including the voltage drop in the conductors.
- Suspect load feeder: makes it possible to attribute harmonic currents, unbalance or starting events to it.
- Several simultaneous points: make it possible to compare and decide whether a disturbance comes from outside or inside.
Practical aspects
The voltage connection must be made with the correct reference: three phases and neutral in a wye system with neutral, or between phases in a system without neutral, configuring the instrument accordingly. Current clamps or coils must be oriented according to the arrow on the sensor, so that the current entering the load has the expected sign. Measure downstream of the protection or section of interest, not at a point where another branch alters the current.
Common errors
- Connecting at a point that is easy to reach rather than where the question lies.
- Reversing the polarity of a clamp, which gives powers with the wrong sign.
- Setting the wrong connection mode (for example, treating a delta system as wye).
- Measuring voltage at one point and current at another, with an impedance between them.
Safety
Connecting to energized busbars, breakers or panels involves electrical risk. It must be done by qualified personnel, with the protective equipment and procedures required by the applicable safety regulations, and respecting the measurement categories of the accessories.