First, the reference
All thresholds are expressed as a percentage of a reference voltage. If this is declared incorrectly (for example, a nominal voltage different from the actual system voltage), events are detected with a bias. The connection, the transformation ratio if instrument transformers are present, and the nominal voltage must be confirmed before starting.
What is configured
- Sag threshold: the level below which a sag is considered to begin.
- Overvoltage threshold: the level above which a swell is recorded.
- Interruption threshold: a very low level interpreted as loss of voltage.
- Hysteresis: the difference between the level that triggers the event and the level that ends it, so that noise near the threshold does not generate fragmented events.
- Transient trigger: by abrupt waveform change, by peak value or by variation from the previous cycle.
- Waveform capture: number of cycles before and after the event (pre-trigger and post-trigger).
How to choose the values
Start from what you want to detect. If you are investigating equipment shutdowns, the thresholds should be as close as, or closer than, the level at which that equipment fails; the equipment tolerance curve is a good guide. Thresholds too close to normal voltage fill the memory with irrelevant events, while wide thresholds miss minor sags that can already affect sensitive loads.
What to check first
- That the nominal frequency and system configuration (wye, delta, number of wires) match the installation.
- That the instrument clock is synchronized, to correlate with records from other devices.
- That the trend averaging interval is separate from event detection, which uses RMS values updated every half cycle.
- That the memory and recording time are sufficient for the campaign.
What the engineer sees in practice
A list of events with timestamp, depth, duration and affected phases, plus waveforms. An excess of events usually indicates thresholds that are too tight or an incorrect reference.
Warning: connecting an analyzer to energized installations involves electrical risk. It must be done by qualified personnel, with the protective equipment and procedures required by the applicable regulations.