Online or line-interactive UPS against grid variations?

An online UPS always feeds the load from the inverter and isolates it from the grid, with no transfer time; a line-interactive UPS passes regulated grid voltage and switches to battery only on a failure, with a brief transfer time.

How they operate

In an online (double-conversion) UPS, power always passes through a rectifier and an inverter: the rectifier feeds the DC bus and the battery, and the inverter generates the output voltage. The load never sees the grid directly, so the output voltage has controlled amplitude and frequency and is isolated from sags, overvoltages, noise and transients. If the grid fails, the battery keeps feeding the bus and there is no interruption.

In a line-interactive UPS, the load is normally fed from the grid through a conditioning stage: a tap-changing voltage regulator or a bidirectional converter corrects slow variations within a certain range. If the grid goes out of tolerance or fails, a switch transfers the load to the inverter and battery. There is a brief transfer time.

Differences in what they protect against

  • Interruptions: both cover them with the battery; only the double-conversion type does so with no transfer.
  • Sags and overvoltages: the line-interactive UPS corrects within its regulation range and transfers to battery outside it; the double-conversion UPS isolates them almost completely.
  • Noise, transients and distortion: the double-conversion UPS isolates better; the line-interactive UPS filters only partially.
  • Frequency: the double-conversion UPS can deliver a stable frequency.

Operating cost

Double conversion has higher losses because all the power is converted twice, and therefore more heat. The line-interactive UPS is more efficient in normal operation and usually costs less. Some double-conversion models include an economy mode that comes close to line-interactive operation.

How to choose

For critical loads that cannot tolerate any transfer (data centers, process equipment, instrumentation), double conversion is advisable. For office equipment or tolerant loads, the line-interactive UPS is usually sufficient. Generator compatibility, load type (some loads are sensitive to the output waveform on battery), power factor and the required autonomy must also be considered. Installation is work for qualified personnel.