How are maximum demand and load factor measured?

Maximum demand is the highest average power calculated over successive demand intervals, and load factor is the ratio of average demand to maximum demand for the period.

What is really being measured

Demand is not instantaneous power. It is the energy consumed during an interval divided by the length of that interval, in other words, the average power. The interval is set by the tariff, the contract or the meter, so the same load profile can yield different maximum demands depending on the window.

How it is determined

  1. The meter accumulates energy (kWh) over consecutive intervals of fixed length.
  2. Each energy value is converted to average power by dividing it by the interval.
  3. Maximum demand is the highest value recorded during the billing or analysis period.

There are fixed windows, which reset at each interval, and sliding windows, which are recalculated continuously. A sliding window can show a higher maximum because it finds the best alignment of a peak with the window.

Load factor

It is calculated as the average demand for the period (total energy divided by total time) divided by the maximum demand. It is a number between zero and one. A value close to one indicates stable consumption; a low value indicates that the installation has peaks that the contracted or installed capacity must cover even though they occur rarely.

What an engineer sees in practice

A load profile with simultaneous motor starts, or with a furnace that switches on all at once, shows isolated peaks that raise maximum demand and lower the load factor. A peak shorter than the interval is diluted in the average, which is why a start lasting a few seconds may not show up in demand even though it does affect instantaneous current and the protection devices.

How to interpret the result

A low load factor is not a defect in itself; it is an invitation to check whether the peaks can be staggered or shifted in time. Demand in kW must be distinguished from apparent demand in kVA, because transformer and cable capacity is limited by current and not only by active power. For measurement, the instrument must use the same interval definition as the criterion it will be compared against.