Direct measurement or instrument transformers in power quality

Direct measurement is limited to voltages and currents within the analyzer's range and measurement category; at higher levels, potential and current transformers are used, which reduce the signals but add ratio error, phase error and frequency response limits.

When to use each option

Direct connection is possible when the system voltage and current are within the ranges of the analyzer and the measurement category of its accessories. At medium and high voltage, or with large currents, reduced signals are measured from transformers already installed or added for the measurement.

Aspect Direct With transformers
Range Limited to that of the instrument Any level, depending on the ratio
Accuracy That of the analyzer and sensors Transformer ratio and angle errors are added
Harmonics Good response if the sensor has it May attenuate or distort high-order components
Safety Contact with energized conductors Isolated signal, but with its own hazards

Points to consider with transformers

  • Ratio and polarity: these must be entered correctly in the analyzer; a scale or polarity error invalidates the power measurement.
  • Burden: a current transformer outside its rated burden loses accuracy or saturates.
  • Saturation: a very high current or a DC component can saturate the core and deform the signal.
  • Frequency response: transformers designed for power frequency do not reproduce high harmonics well. Capacitive dividers may have their own resonances.
  • Current transformer secondary: it must never be left open with the primary energized, because dangerous voltages appear.

Alternative current sensors

Clamps and flexible coils avoid opening the circuit and cover large currents. Flexible coils have good linearity, but lower accuracy at low currents, and they depend on an integrator.

How to decide

If the goal is to evaluate high-frequency harmonics, confirm the bandwidth of the entire chain. If the goal is to see voltage or power trends at fundamental frequency, an existing transformer is usually enough. Always document the accuracy class of the intermediate elements.

Warning: work on energized installations and with instrument transformers involves electrical risk. It must be done by qualified personnel, following the applicable regulations.