- What does radiometric calibration mean?
It means establishing, against reference sources of known temperature, the relationship between the signal the detector delivers and the temperature the camera must display, so that each pixel is a measurement and not just an image.
- What guidance does ASTM E1934 give for electrical and mechanical equipment?
ASTM E1934 is a guide on how to examine electrical and mechanical equipment with infrared thermography: what to consider when planning, performing, documenting, and reporting the inspection.
- What is a delta T in thermography?
It is the difference between the temperature measured at a point of interest and that of a reference, which can be the ambient, a similar component under the same conditions, or the same equipment in another inspection.
- What is a microbolometer?
A microbolometer is an uncooled thermal detector: each pixel is a small isolated membrane that is heated by infrared and changes its electrical resistance, which is converted into a signal.
- What is a reference blackbody?
It is an infrared radiation source with controlled temperature and a known emissivity very close to one, used to verify or adjust the radiometric accuracy of a camera or infrared thermometer.
- What is a spot infrared thermometer used for?
A spot infrared thermometer quickly gives the average temperature of a small area of a surface from a distance, without touching it, which is useful for screening and for inaccessible points.
- What is a thermal gradient in a component?
A thermal gradient is the variation in temperature along a component; its shape indicates where heat is generated and how it dissipates, and it makes it possible to tell a localized fault from general heating.
- What is an infrared inspection window?
An infrared inspection window is a panel permanently installed in an equipment enclosure, transparent to infrared, that allows inspection with the camera without opening the switchboard.
- What is atmospheric transmittance in thermography?
Atmospheric transmittance is the fraction of infrared radiation that passes through the air between the object and the camera; it falls with distance and humidity, and the camera compensates for it with entered parameters.
- What is blackbody radiation?
It is the thermal radiation emitted by an ideal body that absorbs all incident radiation, and it depends solely on the body's temperature; it is the model used to interpret and calibrate the signal of a thermal imaging camera.
- What is emissivity and why does it matter?
Emissivity is the ratio of the radiation a surface emits to that of a blackbody at the same temperature; it matters because low emissivity causes the camera to underestimate temperature.
- What is instantaneous field of view (IFOV)?
IFOV is the angle covered by a single detector pixel; multiplied by distance, it gives the size of the area each pixel sees, and it sets the smallest object that can be measured reliably.
- What is reflected apparent temperature?
Reflected apparent temperature is the equivalent temperature of the ambient radiation that reflects off the object toward the camera; it must be entered so that the measurement subtracts that contribution.
- What is the color palette in a thermal image?
It is the rule that assigns a color or shade of gray on the screen to each temperature value in the scene; it changes only the appearance of the image, not the underlying measurement.
- What is the spectral range of an infrared camera?
Spectral range is the band of infrared wavelengths to which the detector responds; it defines what can be measured, at what temperatures and through what media.
- What is thermal resolution or NETD?
Thermal resolution, or NETD, is the smallest temperature difference the camera can distinguish from the noise of its detector; the lower it is, the smaller the differences it can show.
- Why do camera readings drift over time?
Because the detector, electronics, and optics change slowly with use, temperature, and aging, and the relationship between signal and temperature calibrated at the factory no longer matches reality exactly.
- Why do reflections cause false positives in thermography?
Because low-emissivity surfaces, such as polished metal, reflect radiation from their surroundings, and the camera cannot distinguish between what the object emits and what it reflects from a hotter nearby source.
- Why does a blurry thermal image ruin a diagnosis?
Because in an out-of-focus image the energy of a hot spot is spread over several neighboring pixels, which lowers the measured temperature and can lead to misclassifying the severity of a fault.
- Why does a camera show wrong temperatures in the sun?
Because the sun heats surfaces and reflects off them, and the camera measures both effects along with the equipment's own heat; in addition, sun on the camera itself alters its behavior.
- Why does a hot spot not show up in a low-load inspection?
Because the heating of a defective connection grows with the square of the current; at low load, the power dissipated is so low that the temperature difference stays below what can be distinguished from the surroundings.
- Why does a loose connection heat up?
Because a loose connection has less real contact area and higher electrical resistance, and the current flowing through it dissipates power there in proportion to that resistance and to the square of the current.
- Why does thermography of a closed panel underestimate the actual temperature?
Thermography of a closed panel underestimates the actual temperature because the camera measures radiation from the outer surface, which is cooler than the internal component; the cover or door attenuates the heat and can block infrared radiation.