Definition
Emissivity is a number between zero and one. An ideal blackbody has a value of one: it emits the maximum radiation possible for its temperature. A real surface emits a fraction of that amount. The camera measures radiation, not temperature; to go from one to the other, it needs to know what fraction of what it receives comes from the surface’s own emission.
The relationship with reflection
In an opaque object, what is not emitted is reflected: emissivity plus reflectivity add up to one. That is why a low-emissivity surface is also a mirror for infrared, and the camera captures the reflection of whatever is around it.
What it depends on
- Material: nonmetals (paints, plastics, insulation, ceramics) have high emissivity; polished metals, very low.
- Finish: oxidation and roughness increase it; polishing reduces it.
- Temperature and wavelength: it varies with them to some extent.
- Viewing angle: at very oblique angles it falls noticeably.
What an engineer sees in practice
Two components at the same temperature show very different values if one is bright copper and the other is painted. A new, polished connector can look colder than the oxidized bar next to it, and an error in emissivity translates directly into a temperature error, which is larger the lower the actual emissivity is.
What to check first
- Identify the material and finish of the surface to be measured.
- Set a value in the camera that is consistent with that finish, not the default out of habit.
- If the surface has low emissivity, improve the measurement with a tape or paint of known emissivity, or interpret the result only qualitatively.
- Check the reflected apparent temperature.
Tabulated values are for guidance only; for critical measurements, emissivity is determined in the field.