Why do reflections cause false positives in thermography?

Because low-emissivity surfaces, such as polished metal, reflect radiation from their surroundings, and the camera cannot distinguish between what the object emits and what it reflects from a hotter nearby source.

The physical cause

The radiation reaching the camera from a surface is the sum of what the material emits and what it reflects. The lower the emissivity, the greater the reflected fraction. A shiny metal bar emits little and acts almost like an infrared mirror: it can show the outline of a person, a lamp, a hot motor, or the sun, and that image looks like the bar’s own heat.

How to recognize a reflection

  • When the viewing angle changes, the “hot spot” moves or disappears, whereas real heat stays where it is.
  • It has shapes that correspond to objects in the surroundings, or sharp edges on a smooth surface.
  • It appears on shiny, curved surfaces, and not on areas with paint or tape of known emissivity.
  • If a piece of cardboard or a screen is placed between the suspected source and the surface, the anomaly changes.

Common errors

  • Interpreting a hot patch on a polished cover as an internal defect.
  • Measuring perpendicular to a specular surface: it reflects the camera itself and the person operating it.
  • Using a high emissivity on a shiny metal “to get a reasonable reading,” which hides the problem instead of correcting it.

How to reduce them

  1. Observe from two or more angles and compare.
  2. Measure on areas of higher emissivity, such as painted terminals or a small piece of tape of known emissivity.
  3. Determine the reflected apparent temperature and enter it into the camera.
  4. Shield nearby radiation sources or inspect at times with fewer sources.
  5. Confirm with another technique if the finding is important.

What this says about the method

A diagnosis based on a single image of a shiny surface deserves suspicion. A reflection is not a camera fault: it is a property of the surface that the thermographer must control.