What really happens
The camera is not “wrong” when measuring in the sun: it measures the radiation that arrives, but that radiation no longer represents only the heat generated by the equipment. The sun adds energy in three ways.
- Solar heating: surfaces receiving sun heat up, especially dark ones, and can exceed the temperature of a faulty component in the shade.
- Reflection: on low-emissivity surfaces the sun reflects strongly and appears as a bright area that looks hot.
- Uneven heating: shadows from structures, clouds, and angles of incidence create thermal differences that mask real anomalies.
Effect on the camera
Aiming at or near the sun can damage the detector and leaves saturated images. In addition, a camera exposed to direct sun changes its internal temperature, and the instrument’s compensation has to follow that change. With rapid variations, readings can drift until the equipment stabilizes.
Common errors
- Reporting as an anomaly the part of a piece of equipment that was simply in the sun.
- Inspecting an outdoor disconnect switch at noon and comparing phases with different sun exposure.
- Accepting a reading from shiny metal with the sun directly in front.
- Ignoring wind, which cools the surface and reduces differences.
How to reduce the effect
- Inspect at dawn, at dusk, at night, or under overcast skies, when the solar effect is smaller.
- Change the viewing angle to avoid the sun’s reflection.
- Shade the target and wait for it to cool if possible.
- Compare only components with the same exposure.
- Note wind, cloud cover, and time of day in the report.
Inspections in substations and on energized outdoor equipment are performed by qualified personnel under the corresponding electrical safety regulations.