24/7 emergencies 814 777 6921812 230 6079WhatsApp 811 786 0768
Electrónica MonterreyElectrónica MonterreyLaboratorios Creativeit Talk to an engineer
Menu

How Is Combustible Gas Content Measured?

The combustible gas content of oil is measured by extracting the dissolved gases from a sample and separating them by gas chromatography, with detectors that quantify hydrogen, hydrocarbons and carbon oxides against calibrated standards.

Two steps: extract and quantify

The oil contains the dissolved gases, and they must be transferred to the gas phase before they can be measured. A chromatograph then separates and quantifies them.

Extraction

  • Vacuum extraction: vacuum is applied over a known volume of oil and the released gas is collected.
  • Headspace: the oil is left to equilibrate with a carrier gas in a closed vessel and the gas is analyzed, applying the partition coefficient of each gas.
  • Gas stripping: an inert gas is bubbled through the oil to strip out the dissolved gases.

Extraction efficiency is not the same for all gases, and the method must correct for it so that the final concentration is that of the oil.

Quantification

The extracted gas passes through columns that separate the components. A thermal conductivity detector responds to hydrogen, oxygen and nitrogen; a flame ionization detector responds to hydrocarbons. To measure carbon monoxide and carbon dioxide with the flame detector, both are usually converted to methane with a catalyst before detection. Each gas is identified by its retention time and quantified by its peak area against a curve obtained with certified gas mixtures.

What an engineer sees in practice

The report gives the concentration of each gas, normally in parts per million by volume of gas relative to the volume of oil, referred to standard conditions of pressure and temperature.

What affects accuracy

  1. Sample quality: hydrogen loss or air ingress.
  2. Current calibration with traceable standards.
  3. Leaks in the extraction system.
  4. Periodic verification with control samples or interlaboratory comparisons.

The value is meaningful for diagnosis if it is compared with previous results obtained with the same method.

We do real tests, on video! Watch them on our YouTube channel →

Do you have a problem nobody has been able to measure?

Talk directly to the engineer in charge, with no middlemen.

Talk to an engineer