What is to be measured
The service life of a transformer is largely determined by its solid cellulose insulation. Cellulose consists of long chains of glucose molecules; as it ages, the chains break and the paper loses mechanical strength. The direct indicator of this deterioration is the degree of polymerization (how many units the average chain has), which is measured on a paper sample.
The problem: paper can hardly be sampled
Removing paper requires opening the equipment, so in service the approach relies on degradation products that pass into the oil.
- Furans: these form as cellulose degrades and are measured in the oil. Their concentration is related to the degree of polymerization through empirical correlations.
- Carbon monoxide and dioxide: these accompany the thermal degradation of the paper and are obtained from dissolved gas analysis; their ratio to each other indicates whether the paper is involved in a fault.
- Moisture: water accelerates the hydrolytic aging of cellulose.
- Acidity: acids in the oil and paper contribute to and accelerate the process.
Why it is an estimate and not a measurement
Furans are partitioned between paper and oil, and their quantity changes with oil treatment or replacement, with temperature, and with the type of paper (thermally upgraded paper produces less). In addition, the oil result averages the entire unit, while the real damage is concentrated at the hot spots, which are what actually limit service life.
How to interpret the result
- Use trends, not an isolated sample.
- Combine several indicators rather than relying on just one.
- Consider whether the oil has been treated, filtered, or replaced, because that erases the furan footprint.
- Relate the results to the loading and temperature history.
Cellulose aging increases rapidly with rising temperature, water, and oxygen. A result indicating poor condition must lead to a more detailed assessment, never to a decision based solely on a correlation.