Where twice the frequency comes from
The magnetic force between two surfaces is proportional to the square of the flux density. If the field alternates at line frequency, its square has a component at twice that frequency. In an ideal, perfectly symmetrical motor those forces cancel out, but any asymmetry leaves a net force that vibrates at twice the supply frequency.
Common causes
- Air gap eccentricity: the rotor is not centered relative to the stator, whether statically or dynamically.
- Loose stator or loose core: the laminations or the stack vibrate under the magnetic force.
- Soft foot or distorted base: the frame is distorted and changes the air gap.
- Voltage imbalance or shorted turns: these alter the distribution of forces.
How to tell it apart
The simplest test is to cut the power with the motor still turning. If the vibration at twice line frequency disappears immediately, its origin is electrical, and if it persists while the rotor decelerates, its origin is mechanical. In induction motors, the effect of pole pass sidebands is also seen when the eccentricity is dynamic.
What the engineer sees
A clear peak at twice line frequency, stable over time and often stronger in the radial direction. If it grows with load or with heating, it points to a progressive stator or base problem.
Safety
Disconnecting the power and testing on energized motors must be carried out by qualified personnel, following the applicable regulations and lockout/tagout procedures.