A different kind of stress from the utility supply
The utility supply delivers a sinusoidal voltage. A variable frequency drive generates its output by pulse width modulation: a succession of voltage pulses whose amplitude is that of the DC bus and whose rising edges are very fast. The motor, designed for a sine wave, receives a different kind of stress.
Failure mechanisms
- Reflected wave: the cable and the motor have very different impedances. The fast pulse travels along the cable and is partially reflected on reaching the motor, so the terminal voltage can approach twice the pulse voltage. The effect increases with cable length and edge speed.
- Uneven distribution in the winding: because of the high frequency of the edges, the voltage is not shared evenly among the turns; the first turns of each coil withstand a larger fraction.
- Partial discharges: in small voids or between adjacent turns, the air and the surface ionize, gradually eroding the insulation.
- Additional heating: dielectric and high-frequency losses raise the insulation temperature.
- Common-mode voltage: it produces currents through the bearings and in the shaft, which damage the bearing races even though they are not winding failures.
What the engineer sees
Early failures in relatively new motors, usually turn-to-turn or phase-to-ground, with the damage concentrated in the first coils. Insulation resistance measured with direct current may remain acceptable until shortly before failure, because deterioration from partial discharges shows up mainly under fast pulses.
How it is mitigated
- Motors with insulation designed for drive operation.
- Output reactors or filters that soften the edges or filter the waveform.
- Limiting cable length or using cable suitable for drives, with shielding and correct ground connection.
- Adjusting the switching frequency and attending to the grounding to reduce common-mode voltage.
To diagnose the condition, tests that excite the turn-to-turn insulation and partial discharge measurements are used. These tests are performed by qualified personnel.