Where the fibers come from
The fibers are almost always cellulose, because the transformer is full of paper and pressboard. They can also come from textiles foreign to the equipment.
- Solid insulation: natural shedding of fibers from the paper, accelerated by aging, oil circulation, or vibration.
- Manufacturing and repair: residues from manufacturing or from internal work that were not completely removed.
- Oil handling: dirty hoses, tanks, or containers; rags and unsuitable filters that shed fiber.
- Filter media: a low-quality or saturated cartridge can release material into the very oil it was meant to clean.
- Pumps and cooling circuits: wear of mechanical components generates other types of particles, such as metal, which are studied separately.
Why they are a problem
A dry fiber in clean oil has little effect. But cellulose absorbs water avidly, and a wet fiber is conductive compared with the oil. Under an electric field, fibers and particles align with the field lines and can form a bridge between electrodes, which initiates a discharge. That is why particles matter more when the oil also contains moisture.
What an engineer sees in practice
A dielectric strength test result that falls with moderate moisture, or a high particle count, with fibers visible when a sample is inspected. Visual examination and particle counting indicate size and quantity; microscopy makes it possible to distinguish fibers from metal or carbon.
How to interpret the result
- Identify the particle type before deciding: cellulose, metal, and carbon have different causes.
- Consider the water content of the oil at the same time.
- Confirm that the sample was not contaminated during collection.
- If the origin is handling, closed-circuit filtration with suitable media usually corrects it.
- If the origin is paper aging, correlate with other indicators of insulation condition.