Why hydrogen is the most sensitive gas
The hydrogen molecule (H2) requires the least energy to form when the carbon-hydrogen bonds of the oil molecules break. That is why it appears in low-energy discharges, in thermal faults, and in more severe electrical faults. It is also very mobile, so it diffuses quickly through the oil and escapes easily through gaskets or during sampling.
Frequent origins
- Partial discharges: these are the classic origin. If hydrogen dominates the other gases, discharge in cavities or in high-field zones is a leading hypothesis.
- Localized heating: as the fault temperature rises, hydrogen accompanies hydrocarbons of low and high molecular weight.
- Reactions of water with steel: moisture in contact with freshly oxidized metal surfaces or with certain coatings can release hydrogen without any electrical fault.
- Gassing of the oil without a fault: some oils and combinations with metals generate hydrogen at moderate temperatures, the so-called “stray gassing”.
- External sources: the tap changer, contamination of new oil, or recent repairs can leave residual gases.
What an engineer sees in practice
An isolated value says little. What is useful is the trend: how much it changed between samples and over what time. Sustained, accelerating growth deserves more attention than a level that is high but has been stable for years.
How to interpret the result
- Compare hydrogen with the other combustible gases: methane, ethane, ethylene, acetylene, and carbon monoxide.
- If hydrogen rises alone, think of partial discharges, moisture, or gassing without a fault.
- If it rises together with hydrocarbons, a thermal mechanism is more likely; carbon monoxide and carbon dioxide indicate whether the paper is involved.
- Confirm with a second sample taken with the same technique, to rule out sampling errors.
- Review recent loads, temperatures, and events on the equipment.
Numerical alert criteria are found in the dissolved gas interpretation standards; consult the current edition and the equipment manufacturer’s criteria.