What the presence of acetylene indicates
Acetylene (C2H2) forms in appreciable quantities only when the oil reaches extreme temperatures for an instant, as happens in an arc. In a sealed transformer, its appearance in a history that previously showed none is a signal that demands prompt action.
Mechanisms that produce it
- Arcing and high-energy discharges: between windings, to ground, or between turns. They are usually accompanied by hydrogen and ethylene.
- Very severe thermal faults: traces can appear at the high end of thermal faults.
- Tap changer operation: in oil-type tap changers, each operation produces arcs in the tap changer’s own compartment. If there is communication with the main tank, acetylene migrates and looks like a transformer fault when it is not.
- Residues from repairs or contaminated oil: gas remaining after welding work or filling with oil that already contained gases.
What an engineer sees in practice
Attention focuses not on the absolute figure but on two things: whether acetylene was absent and now exists, and whether it grows between samples. A small amount that holds constant after a known event is very different from one that doubles in consecutive samples.
What to check first
- Repeat the sampling to rule out a handling error or a contaminated batch.
- Compare with the other gases: acetylene with plenty of hydrogen and ethylene points to high energy; with very little of them, to an external source.
- Verify whether the tap changer shares oil with the main tank and whether there have been recent operations.
- Consult records of trips, through-faults, and load changes.
- Increase the sampling frequency until the origin is clarified.
Graphical interpretation methods, such as the Duval triangle, help classify the fault type. Decisions on disconnection or internal inspection must be made by specialists with the complete history, and any switching on the equipment must be done by qualified personnel under the applicable regulations.